Residual Current Devices

Product Overview


Click to enlarge - RCD_Familycallouts3


Residual Current Devices

The Bulletin 1492-RCD line includes Residual Current Devices, also known as Residual Current Circuit Breakers, for detecting and interrupting leakage current to ground. By detecting small leakage currents and disconnecting all ungrounded connectors quickly, RCDs can prevent injury to exposed personnel and damage to equipment.

RCDs are used in series with miniature circuit breakers for additional circuit protection from not only overload and short circuit, but also ground fault. Many short circuits begin as undetected ground faults. Using an RCD in an application may detect problems before costly equipment damage and downtime occurs.

These devices are Type A Residual Current Devices to IEC Standards.


Features


Standards Compliance


Certifications


Catalog Number Explanation

Note:Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; some combinations may not produce a valid catalog number.


1492 - RCDA   2   A   25    
      a b c d e

a
Type
Code Description
RCDA Residual Current Device, Type A

b
Poles
Code Description
2 2-Pole
4 4-Pole

c
Sensitivity I∆n
Code Rated Sensitivity [mA]
A 30
B 100
C 300
D 500

d
Rated Current (In)
Code Current [A]
25 25
40 40
63 63
80 80

e
Delay Option (available on select 4-pole devices)
Code Description
  Can be left blank
S With Delay

  Click to enlarge - 1492-RCD2pole Click to enlarge - 1492-RCD Right4pole
Sensitivity (mA) Rated Current (A) 2-Pole (1-Pole + Neutral) 4-Pole (3-Pole + Neutral)
Standard With Delay
30 25 1492-RCDA2A25 1492-RCDA4A25
40 1492-RCDA2A40 1492-RCDA4A40
63 1492-RCDA4A63
80 1492-RCDA4A80
100 25 1492-RCDA2B25 1492-RCDA4B25
40 1492-RCDA2B40 1492-RCDA4B40 1492-RCDA4B40S
63 1492-RCDA4B63 1492-RCDA4B63S
300 25 1492-RCDA2C25 1492-RCDA4C25
40 1492-RCDA2C40 1492-RCDA4C40 1492-RCDA4C40S
63 1492-RCDA4C63 1492-RCDA4C63S
80 1492-RCDA4C80
500 25 1492-RCDA4D25
40 1492-RCDA4D40
63 1492-RCDA4D63
80 1492-RCDA4D80
Diagram Click to enlarge - 2-pole_diagram Click to enlarge - 4-pole_diagram
  

Accessories

Right Mount
Photo Product Description
‡ ⋆ ∆ 
Contacts Standards Certifications UL/CSA Max.
Current/Voltage
IEC Ratings
Current/Voltage
Cat. No.
Click to enlarge - 189-ASCR3_IMG_9961 Auxiliary/Signal Contact 1 N.O./N.C.
(1 C.O.)
UL 1077
CSA 22.2 No. 235
EN 60947-5-1
GB 14048.5
UL Recognized
CSA Certified
CE Marked
VDE Certified
CCC Certified
1 A @ 480V AC
2 A @ 277V AC
1.5 A @ 125V DC
2 A @ 60V DC
4 A @ 24V DC
2 A @ 230V (AC-14)
1 A @ 400V (AC-14)
1.5 A @ 110V (DC-12)
1 A @ 220V (DC-12)
4 A @ 24V (DC-13)
2 A @ 60V (DC-13)
189-ASCR3
Click to enlarge - ASCR3_wiringdiagram
Click to enlarge - 189-AR3_IMG_9970 Auxiliary Contact 1 N.O./N.C.
(1 C.O.)
UL 1077
CSA 22.2 No. 235
EN 60947-5-1
GB 14048.5
UL Recognized
CSA Certified
CE Marked
VDE Certified
CCC Certified
1 A @ 480V AC
2 A @ 277V AC
1.5 A @ 125V DC
2 A @ 60V DC
4 A @ 24V DC
2 A @ 230V (AC-14)
1 A @ 400V (AC-14)
1.5 A @ 110V (DC-12)
1 A @ 220V (DC-12)
4 A @ 24V (DC-13)
2 A @ 60V (DC-13)
189-AR3
Click to enlarge - AR3_wiringdiagram
Click to enlarge - 189-AR11_IMG_9980 1 N.O. + 1 N.C. UL 1077
CSA 22.2 No. 235
EN 60947-5-1
GB 14048.5
UL Recognized
CSA Certified
CE Marked
VDE Certified
CCC Certified
1 A @ 400V AC
2 A @ 230V AC
1 A @ 50V DC
2 A @ 30V DC
2 A @ 230V (AC-14)
1 A @ 400V (AC-14)
2 A @ 30V (DC-12)
1 A @ 50V (DC-12)
2 A @ 30V (DC-13)
1 A @ 50V (DC-13)
189-AR11
Click to enlarge - AR11_wiringdiagram
Click to enlarge - 189-AR02 2 N.C. UL 1077
CSA 22.2 No. 235
EN 60947-5-1
GB 14048.5
UL Recognized
CSA Certified
CE Marked
VDE Certified
CCC Certified
1 A @ 400V AC
2 A @ 230V AC
1 A @ 50V DC
2 A @ 30V DC
2 A @ 230V (AC-14)
1 A @ 400V (AC-14)
2 A @ 30V (DC-12)
1 A @ 50V (DC-12)
2 A @ 30V (DC-13)
1 A @ 50V (DC-13)
189-AR02
Click to enlarge - AR02_wiringdiagram
Click to enlarge - 189-AR20_IMG_9989 2 N.O. UL 1077
CSA 22.2 No. 235
EN 60947-5-1
GB 14048.5
UL Recognized
CSA Certified
CE Marked
VDE Certified
CCC Certified
1 A @ 400V AC
2 A @ 230V AC
1 A @ 50V DC
2 A @ 30V DC
2 A @ 230V (AC-14)
1 A @ 400V (AC-14)
2 A @ 30V (DC-12)
1 A @ 50V (DC-12)
2 A @ 30V (DC-13)
1 A @ 50V (DC-13)
189-AR20
Click to enlarge - AR20_wiringdiagram
 
‡ A maximum of one C.O. type signal contact, and one C.O. type auxiliary contact OR two C.O. type auxiliary contacts may be installed per 1492-RCD.
⋆ A maximum of one 189-AR11, -AR02, or -AR20 auxiliary contact may be installed per 1492-RCD. They may not be combined with C.O. type contacts.
∆ A maximum of three accessories of any type may be installed per 1492-RCD. The signal contact must be mounted closest to the RCD, then the auxiliary contact(s). For allowed combinations, and installation instructions please contact your local Rockwell Automation sales office or Allen-Bradley distributor.

Bus Bars

1492-RCD Cuttable Bus Bars
Description Pins Pkg. Qty. Cat. No.
⋆ 
2-Phase MCB to RCD 4 10 189-CL204
4-Phase MCB to RCD 8 10 189-CL408
  
⋆  These devices are CE Marked, but not certified to any UL, CSA, or other standard.

1492-RCD Bus Bar Accessories
Description Pkg. Qty. Cat. No.
⋆ 
Terminal Power Feed, 6...25 mm2 10 189-CLT25
Terminal Power Feed, 6...50 mm² 10 189-CLT50
Dedicated Power Feed, 50 mm² 10 189-CLT50D
For 2-phase bus bar‡  10 189-CL3EC
For 4-phase bus bar 10 189-CL4EC
Protective Shroud for unused pins 10 189-CLPS
  
⋆  These devices are CE Marked, but not certified to any UL, CSA, or other standard.
‡  189-CL3EC also used for 2- and 3-phase MCB bus bars.

Click to enlarge - 1492-RCDbusbar_iso1

Approximate Dimensions

Click to enlarge - 1492-RCD_2pole_Dims
2-Pole


Click to enlarge - 1492-RCD4pole
4-Pole


Accessory Approximate Dimensions

Click to enlarge - 189_ASCR3
189-ASCR3


Click to enlarge - 189-ar3
189-AR3


Click to enlarge - 189-AR02_11_20
189-AR11, 189-AR02, 189-AR20


Bus Bar Approximate Dimensions

Note: Dimensions are shown in millimeters (incles). Dimensions are not intended for manufacturing purposes.


2- and 4-Phase Bus Bars for connection to 1492-RCD

Click to enlarge - 189-busbar_RCD

General Data
Poles 2,4
Rated currentIn 25, 40, 63, 80 A
Rated sensitivity I∆n 2-pole 30, 100, 300 mA
4-pole 30, 100, 300, 500 mA
Electrical Ratings
Rated short-circuit strength 10 kA with 63 A gG/gL back-up fuse,
10 kA with 80 A gG/gL back-up fuse for 80 A device
Rated operational voltage Ue per IEC/EN 230/400V AC
Rated voltage Ue per UL 480Y/277V AC
Max. operating voltage of circuit test 254V AC
Min. operating voltage of circuit test 110V
Rated frequency 50/60 Hz
Rated conditional short-circuit 10 kA (SCPD - fuse gG 100 A)
Rated residual breaking capacity 1 kA
Rated impulse withstand voltage Uimp (1.2/50ms) 4 kV
Dielectric test voltage at ind. freq. for 1 min. 2.5 kV
Electrical endurance 10,000 operations
Mechanical
Indicator window Red ON/green OFF
Protection degree Housing IP4X
Terminals IP2X
Environmental
Ambient temperature
(with daily average +35 °C)
-25...+55 °C
Storage temperature -40...+70 °C
Mechanical endurance 20,000 operations
Installation
Terminal type Dual terminal
Cross-section of conductors - solid, stranded, flexible (front/back terminal slot) 25...63 A mm2 25/25 mm2
AWG 18...4 AWG
80 A mm2 35/35 mm2
AWG 18…2 AWG
Cross-section of bus bars (back terminal slot) 25...63 A mm2 10/10 mm2
80 A mm2 16/16 mm2
Tightening torque 25...63 A N∙m 2.8 N∙m
in∙lb 25 in∙lb
80 A N∙m 4.8 N∙m
in∙lb 43 in∙lb
Mounting DIN Rail EN 60715 (35 mm) with fast clip device
Supply Optional
  

Approximate Dimensions and Weight
Dimensions (H x D x W) 2-pole 88 x 67 x 35 mm
4-pole 88 x 67 x 70 mm
Weight 2-pole 200 g (7.1 oz.)
4-pole 350 g (12.3 oz.)
Combination with Auxiliary Elements
Auxiliary contact Yes
Signal contact Yes
  

Power Loss Due to Current

At rated current in Watts

Power Loss Due to Current
Rated Current [A] Power Loss [W]
2-pole 4-pole
25 1 1.3
40 2.4 3.2
63 3.2 4.4
80 8.8 33.3