a
|
Type
|
Code
|
Description
|
RCDA
|
Residual Current Device, Type A
|
e
|
Delay Option (available on select 4-pole devices)
|
Code
|
Description
|
|
Can be left blank
|
S
|
With Delay
|
|
|
|
Sensitivity (mA)
|
Rated Current (A)
|
2-Pole (1-Pole + Neutral)
|
4-Pole (3-Pole + Neutral)
|
Standard
|
With Delay
|
30
|
25
|
1492-RCDA2A25
|
1492-RCDA4A25
|
—
|
40
|
1492-RCDA2A40
|
1492-RCDA4A40
|
—
|
63
|
—
|
1492-RCDA4A63
|
—
|
80
|
—
|
1492-RCDA4A80
|
—
|
100
|
25
|
1492-RCDA2B25
|
1492-RCDA4B25
|
—
|
40
|
1492-RCDA2B40
|
1492-RCDA4B40
|
1492-RCDA4B40S
|
63
|
—
|
1492-RCDA4B63
|
1492-RCDA4B63S
|
300
|
25
|
1492-RCDA2C25
|
1492-RCDA4C25
|
—
|
40
|
1492-RCDA2C40
|
1492-RCDA4C40
|
1492-RCDA4C40S
|
63
|
—
|
1492-RCDA4C63
|
1492-RCDA4C63S
|
80
|
—
|
1492-RCDA4C80
|
—
|
500
|
25
|
—
|
1492-RCDA4D25
|
—
|
40
|
—
|
1492-RCDA4D40
|
—
|
63
|
—
|
1492-RCDA4D63
|
—
|
80
|
—
|
1492-RCDA4D80
|
—
|
Diagram
|
|
|
|
Right Mount
|
Photo
|
Product Description ⋆ ∆
|
Contacts
|
Standards
|
Certifications
|
UL/CSA Max. Current/Voltage
|
IEC Ratings Current/Voltage
|
Cat. No.
|
|
Auxiliary/Signal Contact
|
1 N.O./N.C. (1 C.O.)
|
UL 1077 CSA 22.2 No. 235 EN 60947-5-1 GB 14048.5
|
UL Recognized CSA Certified CE Marked VDE Certified CCC Certified
|
1 A @ 480V AC 2 A @ 277V AC 1.5 A @ 125V DC 2 A @ 60V DC 4 A @ 24V DC
|
2 A @ 230V (AC-14) 1 A @ 400V (AC-14) 1.5 A @ 110V (DC-12) 1 A @ 220V (DC-12) 4 A @ 24V (DC-13) 2 A @ 60V (DC-13)
|
189-ASCR3
|
|
|
Auxiliary Contact
|
1 N.O./N.C. (1 C.O.)
|
UL 1077 CSA 22.2 No. 235 EN 60947-5-1 GB 14048.5
|
UL Recognized CSA Certified CE Marked VDE Certified CCC Certified
|
1 A @ 480V AC 2 A @ 277V AC 1.5 A @ 125V DC 2 A @ 60V DC 4 A @ 24V DC
|
2 A @ 230V (AC-14) 1 A @ 400V (AC-14) 1.5 A @ 110V (DC-12) 1 A @ 220V (DC-12) 4 A @ 24V (DC-13) 2 A @ 60V (DC-13)
|
189-AR3
|
|
|
1 N.O. + 1 N.C.
|
UL 1077 CSA 22.2 No. 235 EN 60947-5-1 GB 14048.5
|
UL Recognized CSA Certified CE Marked VDE Certified CCC Certified
|
1 A @ 400V AC 2 A @ 230V AC 1 A @ 50V DC 2 A @ 30V DC
|
2 A @ 230V (AC-14) 1 A @ 400V (AC-14) 2 A @ 30V (DC-12) 1 A @ 50V (DC-12) 2 A @ 30V (DC-13) 1 A @ 50V (DC-13)
|
189-AR11
|
|
|
2 N.C.
|
UL 1077 CSA 22.2 No. 235 EN 60947-5-1 GB 14048.5
|
UL Recognized CSA Certified CE Marked VDE Certified CCC Certified
|
1 A @ 400V AC 2 A @ 230V AC 1 A @ 50V DC 2 A @ 30V DC
|
2 A @ 230V (AC-14) 1 A @ 400V (AC-14) 2 A @ 30V (DC-12) 1 A @ 50V (DC-12) 2 A @ 30V (DC-13) 1 A @ 50V (DC-13)
|
189-AR02
|
|
|
2 N.O.
|
UL 1077 CSA 22.2 No. 235 EN 60947-5-1 GB 14048.5
|
UL Recognized CSA Certified CE Marked VDE Certified CCC Certified
|
1 A @ 400V AC 2 A @ 230V AC 1 A @ 50V DC 2 A @ 30V DC
|
2 A @ 230V (AC-14) 1 A @ 400V (AC-14) 2 A @ 30V (DC-12) 1 A @ 50V (DC-12) 2 A @ 30V (DC-13) 1 A @ 50V (DC-13)
|
189-AR20
|
|
|
A maximum of one C.O. type signal contact, and one C.O. type auxiliary contact OR two C.O. type auxiliary contacts may be installed per 1492-RCD.
|
⋆ A maximum of one 189-AR11, -AR02, or -AR20 auxiliary contact may be installed per 1492-RCD. They may not be combined with C.O. type contacts.
|
∆ A maximum of three accessories of any type may be installed per 1492-RCD. The signal contact must be mounted closest to the RCD, then the auxiliary contact(s). For allowed combinations, and installation instructions please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
|
1492-RCD Cuttable Bus Bars
|
Description
|
Pins
|
Pkg. Qty.
|
Cat. No. ⋆
|
2-Phase MCB to RCD
|
4
|
10
|
189-CL204
|
4-Phase MCB to RCD
|
8
|
10
|
189-CL408
|
|
⋆ These devices are CE Marked, but not certified to any UL, CSA, or other standard.
|
1492-RCD Bus Bar Accessories
|
Description
|
Pkg. Qty.
|
Cat. No. ⋆
|
Terminal Power Feed, 6...25 mm2
|
10
|
189-CLT25
|
Terminal Power Feed, 6...50 mm²
|
10
|
189-CLT50
|
Dedicated Power Feed, 50 mm²
|
10
|
189-CLT50D
|
For 2-phase bus bar
|
10
|
189-CL3EC
|
For 4-phase bus bar
|
10
|
189-CL4EC
|
Protective Shroud for unused pins
|
10
|
189-CLPS
|
|
⋆ These devices are CE Marked, but not certified to any UL, CSA, or other standard.
|
189-CL3EC also used for 2- and 3-phase MCB bus bars.
|
General Data
|
Poles
|
2,4
|
Rated currentIn
|
25, 40, 63, 80 A
|
Rated sensitivity I∆n
|
2-pole
|
30, 100, 300 mA
|
4-pole
|
30, 100, 300, 500 mA
|
Electrical Ratings
|
Rated short-circuit strength
|
10 kA with 63 A gG/gL back-up fuse, 10 kA with 80 A gG/gL back-up fuse for 80 A device
|
Rated operational voltage Ue per IEC/EN
|
230/400V AC
|
Rated voltage Ue per UL
|
480Y/277V AC
|
Max. operating voltage of circuit test
|
254V AC
|
Min. operating voltage of circuit test
|
110V
|
Rated frequency
|
50/60 Hz
|
Rated conditional short-circuit
|
10 kA (SCPD - fuse gG 100 A)
|
Rated residual breaking capacity
|
1 kA
|
Rated impulse withstand voltage Uimp (1.2/50ms)
|
4 kV
|
Dielectric test voltage at ind. freq. for 1 min.
|
2.5 kV
|
Electrical endurance
|
10,000 operations
|
Mechanical
|
Indicator window
|
Red ON/green OFF
|
Protection degree
|
Housing
|
IP4X
|
Terminals
|
IP2X
|
Environmental
|
Ambient temperature (with daily average +35 °C)
|
-25...+55 °C
|
Storage temperature
|
-40...+70 °C
|
Mechanical endurance
|
20,000 operations
|
Installation
|
Terminal type
|
Dual terminal
|
Cross-section of conductors - solid, stranded, flexible (front/back terminal slot)
|
25...63 A
|
mm2
|
25/25 mm2
|
AWG
|
18...4 AWG
|
80 A
|
mm2
|
35/35 mm2
|
AWG
|
18…2 AWG
|
Cross-section of bus bars (back terminal slot)
|
25...63 A
|
mm2
|
10/10 mm2
|
80 A
|
mm2
|
16/16 mm2
|
Tightening torque
|
25...63 A
|
N∙m
|
2.8 N∙m
|
in∙lb
|
25 in∙lb
|
80 A
|
N∙m
|
4.8 N∙m
|
in∙lb
|
43 in∙lb
|
Mounting
|
DIN Rail EN 60715 (35 mm) with fast clip device
|
Supply
|
Optional
|
|
Approximate Dimensions and Weight
|
Dimensions (H x D x W)
|
2-pole
|
88 x 67 x 35 mm
|
4-pole
|
88 x 67 x 70 mm
|
Weight
|
2-pole
|
200 g (7.1 oz.)
|
4-pole
|
350 g (12.3 oz.)
|
Combination with Auxiliary Elements
|
Auxiliary contact
|
Yes
|
Signal contact
|
Yes
|
|
Power Loss Due to Current
|
Rated Current [A]
|
Power Loss [W]
|
2-pole
|
4-pole
|
25
|
1
|
1.3
|
40
|
2.4
|
3.2
|
63
|
3.2
|
4.4
|
80
|
8.8
|
33.3
|
|